Clear records
history record
PRODUCT
RELATED PRODUCT
APPLICATION
▶ It is suitable for all kinds of control boxes, distribution cabinets and other electrical devices that have high requirements on temperature and humidity in machinery, electric power, chemical industry, instrumentation and textile industries. Can also be used for small space temperature and humidity regulation.
TYPE

▶ 1. QG: Code
▶ 2. JK: Electric cabinet air conditioning
▶ 3. Refrigerating capacity code: (x 10W)
030: Refrigerating capacity is 030 x 10W=300W
▶ 4. A: Standard type
H: High temperature type
▶ 5. W: Hang outside type
R: Hang inside type
X: Embedded type
▶ 6. Power code
The first digit indicates the number of power phases, 1: single phase.
The second and third digits indicate the first two digits of the voltage, 22: voltage is 220V.
The fourth digit indicates the power frequency, 5: 50Hz.
Model | QG -JK-030 | QG -JK-050 | QG -JK-080 | QG -JK-100 | QG -JK-150 | QG -JK-250 | QG -JK-350 | |
Item | Unit | |||||||
Cooling Capacity | W | 300 | 500 | 800 | 1000 | 1500 | 2500 | 3500 |
Power | V/Hz | 220V 50Hz | ||||||
Rated Power | W | 288 | 420 | 550 | 670 | 900 | 1100 | 1300 |
Rated Current | A | 1.5 | 2.1 | 2.5 | 3 | 4 | 5 | 6 |
Refrigerant (standard) | R134a | R22 | R22 | |||||
Temperature Control | ℃ | 20-40 | ||||||
The Use of Ambient Temperature | ℃ | ≤45 | ||||||
Refrigerant (optional) | R134a | R410a | R410a | R410a | R410a | |||
Noise | d(BA) | ≤58 | ≤62 | ≤62 | ≤62 | ≤62 | ≤62 | ≤62 |
Protection Grade | IP | IP44 | ||||||
Dimensions | MM | 320*565*170 | 345*580*170 | 365*610*164 | 365*610*164 | 400*905*205 | 405*1105*280 | |
Contact Us